Good morning, everyone calling to order this meeting of uh the committee of the whole um time is 1119 on August 13th.

0:11

Um taking attendance, Vice Chair Clements, yeah.

0:15

Majority leader Holstein president.

0:19

I heard that uh minority leader concealer, uh majority with uh Williams, uh minority with Nolan.

0:29

Yeah, legislative bar.

0:32

That's not so important after all those titles.

0:34

Okay, um here legislator puja.

0:44

Here we should no that was far.

0:47

Um uh legislator Woodson Sands present.

0:51

Uh let's say our memorial here, let's set a Mat and BR.

0:56

Legislator Pierce.

0:58

Present, legislator Smith here.

1:02

Uh Legislator Chubiola, present legislator Uli.

1:06

Legislator Alvarado, present, legislator Williams Johnson on the way.

1:14

All right.

1:14

Um, and I am present tonight, today rather.

1:18

Uh we're here to discuss the Yonkers joint water uh wastewater treatment plan, power failure and resulting uh sewage spill that uh impacted our community that's raised so many questions.

1:32

Um we are joined today by the Department of Environmental Uh Facilities Commissioner Vincent Kapicki.

1:39

Vincent, do you want to join us at the table?

1:42

Uh first Deputy Commissioner Lou Patron uh as well as Peter McCartney.

1:48

You're gonna join us at the table.

1:51

Uh Emily Saltzman's also here, and you're welcome to choose um so um would you like to start with the presentation and then we can uh get a few questions follow?

2:07

Um sure.

2:09

Uh morning everyone.

2:12

It's in Kopicki, Commissioner for DEF.

2:20

So I think probably the best way to start is just to give a little background about how the treatment plant works, how the author plant works.

2:28

I know a lot of legislators have been to the plant.

2:31

Um if you haven't, please let me know.

2:34

We'd love to give you a tour of the facility.

2:37

Um so the plant uh treats uh uh sewage from approximately 500,000 uh residents of Westchester County.

2:49

And just to give you an idea of the how much we process, um for 2025 we processed uh a little under 24 billion gallons, and so far this year, uh a little over 12 billion gallons.

3:04

So the way the treatment plant works is flow comes in, it comes in, and the first thing it hits is the uh the screenings, and that's where it takes out um all of the heavy the rags, heavy pieces.

3:18

Uh there's bar screens that uh that the scrapers that pull it up and we we take that off site.

3:25

Uh from there, um, and and just so you know, you know, during this event, the uh um those were always operational.

3:37

So we have emergency generators just for the screenings, so those continue to operate throughout the power event.

3:45

Uh after that, it goes to our primary settling tanks, which our deep tanks and all the solids uh basically go to the bottom.

3:55

So there's uh flights that that move and take the uh skim off the top, and the solids will settle.

4:04

So excuse me.

4:06

Sorry.

4:07

Um a lot of things happen this morning, so I'm sorry.

4:11

I'm a little uh uh after the the settling tanks, uh it goes to the erasing tank where we feed air into the system.

4:22

Uh the air feeds the bugs, which basically break down it's a biological you know, uh process that treats the waste, and from there it goes to the final settlement tanks, which settle again all solids, and it goes to finally the chlorine contact tanks where we do chlorination and declorination and then discharge the which is now not sewage, sewage comes in at the end.

4:48

It's treated effluent wastewater.

4:51

So that's a basically an overview of how the plant works.

4:57

Our permit limit is 85% removals.

5:01

We typically achieve 94 to 96% removals, which is great.

5:06

We do in excess of what we are required to do.

5:13

So now I'd like to talk a little bit about what happened, you know, on starting on July 2nd.

5:21

So at approximately 9 o'clock PM on July 2nd, we experienced a voltage reduction from Con at about an 8% voltage reduction.

5:34

DEF was unaware that this voltage reduction was taking place.

5:40

So from and we actually did not find out about the voltage reduction until the next morning around 11 30 a.m.

5:52

Uh from 9 to 10.

5:55

Our planned personnel were resetting all the equipment, uh standard operating procedure.

6:02

Um at 10 o'clock, uh while we were resetting the equipment, we were bringing on what we call it's the roots blower, it's one of our larger um blowers for the aeration tanks.

6:17

It's uh 4160 volt, it's 1750 horsepower, so it's a lot of draw, big blower.

6:28

Put that on, and the plant went black.

6:32

So we had a total blackout at that point.

6:35

Um at that point, we um we called in restrictions.

6:42

We typically don't have electricians on overnight.

6:46

It's a smaller crew, uh, some operators maintenance mechanics, but it's not necessary to have uh electricians on the overnight.

Discussion Breakdown — Share of Meeting
Water And Wastewater Management█████████████████████████████████████████████54%
Public Safety█████████████████20%
Engineering And Infrastructure████████9%
Public Engagement████5%
Technology and Innovation████5%
Community Engagement███4%
Procedural██2%
Environmental Protection1%
Summary of Proceedings

Committee of the Whole Meeting on Yonkers Wastewater Treatment Plant Power Failure – August 13, 2026

On August 13, 2026, the Westchester County Board of Legislators Committee of the Whole convened to discuss the power failure and resulting partially treated effluent discharge at the Yonkers Joint Wastewater Treatment Plant that occurred over the July 4th holiday weekend. The meeting featured a detailed presentation from Department of Environmental Facilities (DEF) Commissioner Vincent Kopicki and First Deputy Commissioner Louis Vetrone, followed by extensive questioning from legislators. Key topics included the root cause of the failure (an unannounced 8% voltage reduction by Con Edison that damaged a breaker), the response timeline, communications breakdowns with Con Edison, the fact that the released effluent met all permit limits despite being only partially treated, and lessons learned for future prevention.

Discussion Items

  • Commissioner Kopicki presented an overview of the plant: it treats sewage from approximately 500,000 residents, processing nearly 24 billion gallons in 2025. The plant normally achieves 94-96% removal, exceeding its 85% permit limit. He explained that on July 2 at 9:00 PM, Con Edison implemented an 8% voltage reduction (brownout) without notifying DEF. Between 9-10 PM, staff reset equipment, but at 10 PM a large 1,750-horsepower roots blower was brought online, causing a total plant blackout. The plant’s emergency generators were not triggered because they only activate on complete power loss, not on voltage reduction. DEF contacted Con Edison at 11:23 PM and 11:53 PM but received no response until the following morning. Electricians worked overnight in the dark and heat, and eventually found a damaged breaker for the roots blower as the cause of repeated trips. At 11:00 AM on July 3, they implemented a workaround using construction-site generators, restoring primary treatment. Full power and full secondary treatment resumed at 1:45 PM on July 3. Con Edison did not restore full utility power until July 6. Throughout the event, the plant met all its permit limits (85% removal) for CBOD5, TSS, fecal coliform, and other parameters. Commissioner Kopicki stressed that the discharge was partially treated effluent, not raw sewage. DEF notified DEC at 12:55 AM on July 3 and issued an NY Alert at 1:09 AM. The DEC subsequently issued a notice of violation; DEF has submitted a corrective action plan focusing on improved communication and is awaiting closure. DEF has since met with Con Edison to update contact lists (adding 30 DEF personnel) and is exploring voltage-boosting equipment and protocols for proactive generator switching during anticipated voltage reductions.
  • Legislators asked a series of questions, focusing heavily on Con Edison’s role and communication failures. Several legislators (Alvarado, Williams, Pierce, Ulaj, Tobiello, Holstein, Nambiar) expressed frustration that Con Edison did not notify DEF before the voltage reduction, did not respond to emergency calls, and did not come to the site. They noted that the plant is designated a critical infrastructure facility but was not prioritized. Legislators called for requiring Con Edison to hold critical infrastructure meetings during heat waves and to improve notification (texts, calls, etc.). Some legislators raised concerns about the DEC violation, the need for a public after-action report, and the importance of testing for swimming and recreation safety. Others (Legislator Bar, Nolan, Nader) emphasized the need for better internal county communications to avoid mixed messages about river safety. Legislator Williams Johnson questioned whether the emergency response could be improved by having electricians on-site overnight during summer months. Legislator Tobiello raised the possibility of requiring Con Edison to isolate critical infrastructure from voltage reductions, though DEF noted that is not currently feasible. Legislator Puja asked for a walkthrough of how the plant would handle a similar event today. Commissioner Kopicki responded that with advance notification, they would bring in electricians, take large equipment offline, and use generator power proactively. Multiple legislators expressed appreciation for the dedication of DEF staff who worked around the clock, including those who returned from vacation.
  • Several legislators (Alvarado, Tobiello, Nader) pressed for follow-up meetings with the Department of Health to discuss water testing, odor issues, and broader infrastructure concerns. Legislator Pierce raised the issue of combined sewer overflows and the need for municipalities to fix their stormwater systems to reduce the burden on the Yonkers plant. Commissioner Kopicki noted ongoing capital projects totaling $68 million at the Yonkers plant (with an additional $400 million in design for a complete electrical upgrade and an anaerobic digester gas engine project expected online in January 2027).

Key Outcomes

  • No formal votes were taken; the meeting was informational and deliberative.
  • DEF will continue working with Con Edison to finalize new communication protocols and explore voltage-boosting equipment for the plant.
  • DEF will review the possibility of adding voltage-sensing equipment that could alert plant staff to power reductions independently of Con Edison.
  • Legislators expressed intent to involve the state delegation and Public Service Commission to hold Con Edison accountable for communication failures and to advocate for critical infrastructure protections.
  • The committee indicated a future meeting with the Department of Health will be scheduled to address water quality testing, beach advisories, and broader environmental concerns raised by the incident.
  • DEF committed to informing the committee when the DEC notice of violation is formally closed and to providing updates on the electrical upgrade project.

Meeting Transcript

Good morning, everyone calling to order this meeting of uh the committee of the whole um time is 1119 on August 13th. Um taking attendance, Vice Chair Clements, yeah. Majority leader Holstein president. I heard that uh minority leader concealer, uh majority with uh Williams, uh minority with Nolan. Yeah, legislative bar. That's not so important after all those titles. Okay, um here legislator puja. Here we should no that was far. Um uh legislator Woodson Sands present. Uh let's say our memorial here, let's set a Mat and BR. Legislator Pierce. Present, legislator Smith here. Uh Legislator Chubiola, present legislator Uli. Legislator Alvarado, present, legislator Williams Johnson on the way. All right. Um, and I am present tonight, today rather. Uh we're here to discuss the Yonkers joint water uh wastewater treatment plan, power failure and resulting uh sewage spill that uh impacted our community that's raised so many questions. Um we are joined today by the Department of Environmental Uh Facilities Commissioner Vincent Kapicki. Vincent, do you want to join us at the table? Uh first Deputy Commissioner Lou Patron uh as well as Peter McCartney. You're gonna join us at the table. Uh Emily Saltzman's also here, and you're welcome to choose um so um would you like to start with the presentation and then we can uh get a few questions follow? Um sure. Uh morning everyone. It's in Kopicki, Commissioner for DEF. So I think probably the best way to start is just to give a little background about how the treatment plant works, how the author plant works. I know a lot of legislators have been to the plant. Um if you haven't, please let me know. We'd love to give you a tour of the facility. Um so the plant uh treats uh uh sewage from approximately 500,000 uh residents of Westchester County. And just to give you an idea of the how much we process, um for 2025 we processed uh a little under 24 billion gallons, and so far this year, uh a little over 12 billion gallons. So the way the treatment plant works is flow comes in, it comes in, and the first thing it hits is the uh the screenings, and that's where it takes out um all of the heavy the rags, heavy pieces. Uh there's bar screens that uh that the scrapers that pull it up and we we take that off site. Uh from there, um, and and just so you know, you know, during this event, the uh um those were always operational. So we have emergency generators just for the screenings, so those continue to operate throughout the power event. Uh after that, it goes to our primary settling tanks, which our deep tanks and all the solids uh basically go to the bottom. So there's uh flights that that move and take the uh skim off the top, and the solids will settle. So excuse me. Sorry. Um a lot of things happen this morning, so I'm sorry. I'm a little uh uh after the the settling tanks, uh it goes to the erasing tank where we feed air into the system. Uh the air feeds the bugs, which basically break down it's a biological you know, uh process that treats the waste, and from there it goes to the final settlement tanks, which settle again all solids, and it goes to finally the chlorine contact tanks where we do chlorination and declorination and then discharge the which is now not sewage, sewage comes in at the end. It's treated effluent wastewater. So that's a basically an overview of how the plant works. Our permit limit is 85% removals. We typically achieve 94 to 96% removals, which is great. We do in excess of what we are required to do. So now I'd like to talk a little bit about what happened, you know, on starting on July 2nd. So at approximately 9 o'clock PM on July 2nd, we experienced a voltage reduction from Con at about an 8% voltage reduction. DEF was unaware that this voltage reduction was taking place.

SUMMARIZED BY OPENPUBLICA AI
TRANSCRIPT VIA PUBLIC VIDEO
openpublica.com